Sprinkler hazard classification in Singapore: SS CP 52 explained

How sprinkler hazard classes work under SS CP 52 in Singapore, which buildings need sprinklers under the SCDF Fire Code 2023, and how the class drives the design.

Newham engineering team · M&E estimators and fire protection engineers4 min read

Sprinkler hazard classification sorts each area of a building by its fire load: how much combustible material it holds and how quickly a fire would spread. The class then sets almost everything else in the design: the design density (water per square metre), the area of operation the system must supply at once, sprinkler spacing and the water supply. In Singapore it follows SS CP 52, which the SCDF Fire Code requires. The code runs from light occupancies through Ordinary Hazard groups to high hazard process and storage. Getting the class right first matters because a wrong class makes every calculation after it wrong.

This guide explains the concept and the SCDF Fire Code 2023 requirements as published in October 2026. SS CP 52 is a copyrighted Singapore Standard: buy the current edition from the Singapore Standards eShop and design to the edition that applies to your project. This guide does not reproduce its tables.

Which buildings need sprinklers

Before classifying, confirm sprinklers are required at all. Clause 6.4.1 of the SCDF Fire Code 2023 sets the main triggers:

Trigger Requirement
Compartmentation Sprinklers wherever the compartment limits in Table 3.2A cannot be met
Height Every storey of a building over 24 m habitable height, except Purpose Groups I and II
Basements All basement storeys, except Purpose Groups I and II; cross-ventilated basements and some residential car parks can be relaxed under conditions
Factories and warehouses Triggered by, among others, more than 3 storeys, a large compartment area or cubical extent, engineered smoke control or high-bay storage
Atriums Sprinklers up to 18 m high; above that, water monitors, deluge or extended-throw sprinklers
Mixed residential towers Non-residential parts above 24 m, and those not compartmented from the basement, under the conditions in the clause

How the hazard classes are arranged

SS CP 52 groups occupancies broadly like this. Use the code for the exact names, criteria and examples:

Group Typical character What changes in the design
Light hazard Low fire load, little combustible material, such as some residential and institutional areas The lowest density and smallest area of operation
Ordinary Hazard groups (the Fire Code refers to Groups I, II and III) Moderate fire load, from offices and restaurants up to retail, car parks and some manufacturing Density and area of operation step up with each group
High hazard: process Processes with fast-spreading fires, such as some plastics and rubber manufacturing Much higher densities and larger design areas
High hazard: storage Goods stored high or densely, where storage height and arrangement drive the design Design depends on the commodity, storage height and method; in-rack sprinklers may be needed

Water demand by Ordinary Hazard group

The Fire Code does not reproduce SS CP 52's density tables, but clause 6.4.7, on reduced water storage for existing buildings up to 60 m, quotes the system demands from SS CP 52:

Ordinary Hazard group System demand quoted in the Fire Code Tank, reliable inflow Tank, unreliable inflow
Group I 540 L/min 12.5 m³ 16.2 m³
Group II 1,000 L/min 25.0 m³ 30.0 m³
Group III 1,350 L/min 37.5 m³ 40.5 m³

These tank figures apply only to that reduced-storage case for existing buildings, and each is the greater of the table value or 30 minutes of pump running. New buildings, storage risks and chemical processes are excluded. New designs are proven by full hydraulic calculation. The Fire Code also allows combined sprinkler and wet riser systems for ordinary hazard classifications (clause 6.4.8).

How to classify a building, step by step

  1. List every area and its use. Use the architectural plans and the owner's intended use, not just room names.
  2. Note what is stored and how high. Storage height and arrangement can move an area into a high hazard storage class.
  3. Assign a class to each area using SS CP 52's criteria and examples.
  4. Check boundaries between classes. Decide where one class ends and another begins, and whether a higher class needs to extend into neighbouring areas.
  5. Find the most demanding area. It sets the water supply and the pump duty.
  6. Record the basis. Write the classification and its reasons into the design report, so the reviewer and future tenants can see it.

Common mistakes

  • Classifying by room name. A "store" might hold paper archives or flammable goods. Classify by what is there.
  • Ignoring storage height. Racking added after handover can push an area out of the class it was designed for.
  • Carrying values from an old job. Densities and areas come from the edition in force, not a previous project.
  • Forgetting tenant changes. A retail fit-out or a change of use can need re-classification and a new calculation.
  • One class for the whole building. Mixed-use buildings need each area classified separately.
  • Missing the supply check. The most demanding area must be supplied, not the largest.

Related guides

How Newham can help

Newham's fire protection design service prepares sprinkler layouts to SS CP 52 across hazard classifications, with hydraulic calculations, fire pump selection and submission drawings formatted for SCDF. Newham prepares the design and drawings. It is not a QP: where the submission needs Professional Engineer endorsement, Newham coordinates review by a Singapore-registered PE, quoted separately. Book a call to scope a package.

FAQ

Common questions

What is sprinkler hazard classification?

It is the step in sprinkler design that groups each area by how much combustible material it holds and how fast a fire would grow. The class sets the design density, the area the system must be able to supply at once, the water supply and the sprinkler spacing. In Singapore it follows SS CP 52.

What hazard classes does SS CP 52 use?

SS CP 52 moves from the lightest occupancies through several Ordinary Hazard groups to high hazard process and storage risks. The SCDF Fire Code itself refers to Ordinary Hazard Groups I, II and III under SS CP 52. Check the exact class names and criteria in the edition of SS CP 52 that applies to your project.

Which buildings need sprinklers in Singapore?

Under clause 6.4.1 of the SCDF Fire Code 2023, sprinklers are needed where the compartmentation limits in Table 3.2A cannot be met, on every storey of buildings over 24 m habitable height (except Purpose Groups I and II), and in all basements (except Purpose Groups I and II, with limited relaxations). Factories, warehouses and atriums have further triggers.

What water demand does an Ordinary Hazard system need?

The Fire Code's clause on reduced water storage for existing buildings quotes system demands from SS CP 52 of 540 L/min for Ordinary Hazard Group I, 1,000 L/min for Group II and 1,350 L/min for Group III. New designs are confirmed by full hydraulic calculation.

Can a building have more than one hazard class?

Yes. Offices, car parks, retail and storage areas in one building are often classified differently. Each area is designed to its own class, and the water supply must meet the most demanding one.